Click here to search our site.  
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
Rasmi Products:Customer Specifics:Fuji Electric:FRN G11S and FRN P11S
 
EFL-G11 Range
 
  • The EFL-G11 range, especially for Fuji FRENIC5000 G11S and P11S Series inverters up to 22kW.
  • Help to ensure EMC compliance of machinery and installations using G11S and P11S drives.
  • Footprint filters mount between the inverter and the panel, saving valuable space inside wiring cabinets.
  • All filters are designed and manufatured to UL requirements and are CE marked.
 

 

 

 

Applied
FRN-G11S
Inverter
Applied
FRN-P11S
Inverter
Filter
Part No
Rated
Current
Leakage
Current
Nom / Max
External
L x W x H
(mm)
Mount
Dims
X x Y
(mm)
Inverter
Fixing
Price
(£)
FRN-0.4G11S-4EN
FRN-0.75G11S-4EN
EFL-0.75G11-4
5A
0.3 / 40mA
320x116x42
293x90
4XM5
FRN-1.5G11S-4EN
FRN-2.2G11S-4EN
EFL-4.0G11-4
12A
0.3 / 40mA
320x116x42
293x90
4XM5
FRN-5.5G11S-4EN
FRN-7.5G11S-4EN
FRN-5.5P11S-4EN
FRN-7.5P11S-4EN
EFL-7.5G11-4
35A
0.3 / 40mA
320x155x45
293x105
4XM5
FRN11G11S-4EN
FRN15G11S-4EN
FRN11P11S-4EN
FRN15P11S-4EN
EFL-15G11-4
50A
0.3 / 40mA
341x225x48
311x167
4XM6
FRN18.5G11S-4EN
FRN22G11S-4EN
FRN18.5P11S-4EN
FRN22P11S-4EN
EFL-22G11-4
72A
0.3 / 40mA
480x250x70
449x185
4XM6

 

Earth Leakage Measurements
For three phase applications - under normal conditions, with the three phases balanced, earth leakage currents are extremely small - the max values stated are worst possible values such as would occur momentarily during switch on or failure of one or two phases.

Design and Test Criteria
Generally with motor drive systems, the emission levels are greatly affected by the length of the cable between the drive itself and the motor - longer cables will cause considerably higher emissions.
The inverter / filter combinations here, have been designed and tested to achieve compliance to :-
EN 55022:1994, Class B for use in domestic / light industrial environments (Equivelant to the RF emissions tests of Power Drive Standard EN 61800-3:1996 for drives with <25A input current) when fitted with up to 25m motor output cable and to EN 55011:1991 Group 1, Class A for use in industrial environments (Equivelant to the RF emissions tests of Power Drive Standard EN 61800-3:1996 for drives with >25A input current) when fitted with up to 50m motor output cable.

 
 
 
Rasmi Products:Customer Specifics:Fuji Electric:FRN G11S and FRN P11S