| Rasmi Products:Customer Specifics:Moeller:FP 300 and RF 300 |
| |
| FP 300 and RF 300 Range |
| |
|
- The FP-300 and RF-300 ranges, especially for Moeller DF6 and DV6 Series inverters.
- Help to ensure EMC compliance of machinery and installations using DF6 and DV6 drives.
- Footprint filters mount between the inverter and the panel, saving valuable space inside wiring cabinets. Block filters mount beside the inverter.
- All filters are designed and manufatured to UL requirements and are CE marked.
- Ex stock. Delivery within 3 days.
|
| |
| Footprint Type Dimensions |
RF Block Type Dimensions |
.gif)
|
|
| |
Applied
DF6
Inverter |
Applied
DV6
Inverter |
Filter Part No |
Rated Current |
Max Rated Voltage |
Leakage Current
Nom / Max |
External
L x W x H(mm) |
Mount Dims
X x Y |
Inverter Fixing |
Price (£) |
|
DV6 340 075
DV6 340 1K5
DV6 340 2K2
DV6 340 4K0
DV6 340 5K5 |
FP 3016-300 |
16A |
3ph, 480V |
0.5 / 40mA |
305 x 152 x 45 |
290 x 110 |
4 x M5 |
|
DF6 340 11K
DF6340 15K |
DV6 340 7K5
DV6 340 11K |
FP 3040-300 |
40A |
3ph, 480V |
0.5 / 40mA |
315 x 213 x 53 |
300 x 170 |
4 x M6 |
|
DF6 340 18K5
DF6 340 22K
DF6 340 30K |
DV6 340 15K
DV6 340 18K5
DV6 340 22K |
FP 3077-300 |
77A |
3ph, 480V |
0.5 / 42mA |
459 x 253 x 60 |
444 x 210 |
4 x M6 |
|
0 |
|
|
|
|
|
|
|
|
|
DF6 340 37K |
DV6 340 30K |
RF 3092-300 |
92A |
3ph, 480V |
0.5 / 42mA |
400 x 105 x 195 |
384 x 65 |
- |
|
DF6 340 45K
DF6 340 55K |
DV6 340 37K
DV6 340 45K
DV6 340 55K |
RF 3150-300 |
150A |
3ph, 480V |
0.5 / 40mA |
479 x 110 x 240 |
464 x 80 |
- |
|
|
| |
| |
Design and Test Criteria
Generally with motor drive systems the emission levels are greatly affected by the length of the cable between the drive itself and the motor - longer cables will cause considerably higher emissions.
These inverter / filter combinations have been designed and tested to achieve compliance to :-
EN 55022:1994, Class B for use in domestic / light industrial environments (equivalent to the RF emissions tests of Power Drive Standard EN 61800-3:1996 for drives with <25A input current) when fitted with up to 25m motor output cable and to EN 55011:1991 Group 1, Class A for use in industrial environments (equivalent to the RF emissions tests of Power Drive Standard EN 61800-3:1996 for drives with >25A input current) when fitted with up to 50m motor output cable. |
| |
| |
| |
All items are Ex-Stock, delivery made within 3 days of receipt of order.
Quantity discount available. |
|
|
| |