Click here to search our site.  
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
Rasmi Products:Standard Ranges:DLC Power Line Filters:RF 3xxx - DLC Three Phase Filters
 
RF 3xxx - DLC Three Phase Filters
 
 
 
Dimensions  
Case Style
L
W
H
X
Y
Mount
C
250
110
60
238
76
M6
D
270
140
60
258
106
M6
E
270
140
90
258
106
M6
F
365
180
90
338
146
M6
G
435
200
130
408
166
M6
H
495
200
160
468
166
M6
J
587
250
205
560
170
M6
N
688
364
180
640
300
M8
 
Rated Voltage: Line - Line 440 - 550V, 50-60Hz @ 40°C
Part Number
Drive Input (A)
Drive Output (kW)
Terminal Type
Max Cable (mm2)
Leakage Current (mA) Nom / Max
Power Loss (W)
Case Style
Weight (kg)
Price
(£)
RF 3006-DLC
6
1.5
Shrouded
6
0.5/27
8
C
1.6
RF 3012-DLC
12
3.7
Shrouded
6
0.5/27
10
C
1.6
RF 3020-DLC
20
5.5
Shrouded
10
0.5/27
15
D
2.2
RF 3040-DLC
40
11
Shrouded
10
0.5/27
30
D
2.4
RF 3060-DLC
60
18.5
Shrouded
16
0.5/27
51
E
3.5
RF 3070-DLC
70
22
Shrouded
25
0.5/27
44
F
7.5
RF 3100-DLC
100
30
Shrouded
35
0.75/130
69
G
13.8
RF 3120-DLC
120
37
Shrouded
35
0.75/130
45
G
13.8
RF 3170-DLC
170
55
Shrouded
95
0.75/130
80
H
23.5
RF 3230-DLC
230
75
Stud
M12
1.3/150
50
J
41
 
RF 3280-DLC
280
90
Stud
M12
1.3/150
60
J
45
 
RF 3400-DLC
400
132
Stud
M16
1.3/150
80
J
50
 
RF 3480-DLC
480
160
Stud
M16
1.3/150
90
J
50
 
RF 3600-DLC
660
230
Tag
M16
1.3/150
130
N
85
 
RF 3880-DLC
880
315
Tag
M16
1.3/150
210
N
90
 
RF 3990-DLC
1000
330
Tag
M16
1.3/150
300
N
90
 
 
Performance
The graph below shows typical improvements in conducted emissions achieved from the fitting of an RF 3040-DLC filter to a 11kW, three phase AC Inverter running an 11kW motor with 25m screened motor cable.
 
Typical Circuit Schematic

 

 
Rasmi Products:Standard Ranges:DLC Power Line Filters:RF 3xxx - DLC Three Phase Filters

 


Original Layout & Artwork by