Click here to search our site.  
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
Rasmi Products:Customer Specifics:Siemens:RF-MM4
 
RF-MM4 200-250V Three Phase Range
 
  • The MM4 range, especially for Siemens MicroMaster Series inverters.
  • Help to ensure EMC compliance of machinery and installations using MicroMaster 420, 430 and 440 Series three phase drives.
  • Footprint filters mount between the inverter and the panel, saving valuable space inside wiring cabinets.
  • All filters are designed and manufatured to UL requirements and are CE marked.
Applied
MM420 Inverter 6SE6420-2U
Applied MM430 Inverter 6SE6430-2U
Applied MM440 Inverter 6SE6440-2U
Filter Part No
Rated Current
Max Rated Voltage
Leakage Current Nom / Max
External
L x W x H
(mm)
Mount Dims
X x Y
(mm)
Inverter Fixing
Price (£)
C11-2AA0
C12-5AA0
C13-7AA0
C15-5AA0
C17-5AA0
C11-2AA1
C12-5AA1
C13-7AA1
C15-5AA1
C17-5AA1
RF 3006-MM4
6A
3ph, 250V
0.1/7mA
200x73x40
187x56
2xM4
C21-1BA0
C21-5BA0
C22-2BA0
C21-1BA1
C21-5BA1
C22-2BA1
RF 3015-MM4
15A
3ph,250V
0.5/40mA
213x149x40
200x120
4xM4
C23-0CA0
C24-0CA0
C25-5CA0
C23-0CA1
C24-0CA1
C25-5CA1(CT)
RF 3023-MM4
23A
3ph,250V
0.5/40mA
245x195x50
232x156
4xM4
C25-5CA1(VT)
RF 3035-MM4
35A
3ph, 250V
0.5/40mA
245x195x50
232x156
4xM4
 
RF-MM4 380-480V Three Phase Range
 
Applied
MM420 Inverter 6SE6420-2U
Applied MM430 Inverter 6SE6430-2U
Applied MM440 Inverter 6SE6440-2U
Filter Part No
Rated Current
Max Rated Voltage
Leakage Current Nom / Max
External
L x W x H
(mm)
Mount Dims
X x Y
(mm)
Inverter Fixing
Price (£)
D13-7AA0
D15-5AA0
D17-5AA0
D21-1AA0
D21-5AA0
D13-7AA1
D15-5AA1
D17-5AA1
D21-1AA1
D21-5AA1
RF 3006-MM4
6A
3ph, 480V
0.1/7mA
200x73x40
187x56
2xM4
D22-2BA0
D23-0BA0
D24-0BA0
D22-2BA1
D23-0BA1
D24-0BA1
RF 3015-MM4
15A
3ph,480V
0.5/40mA
213x149x40
200x120
4xM4
D25-5CA0
D27-5CA0
D31-1CA0

D27-5CA0
D31-1CA0
D25-5CA1
D27-5CA1
D31-1CA1(CT)
RF 3023-MM4
23A
3ph,480V
0.5/40mA
245x195x50
232x156
4xM4
D31-5CA0
D31-1CA1(VT)
RF 3035-MM4
35A
3ph, 480V
0.5/40mA
245x195x50
232x156
4xM4

 

UL approval documentation and EMC Test Certificates from Independent Test House.

Filter Installation Notes
To conform to EMC directives, it is essential that good wiring practice is observed and that all installation recommendations are followed.

      • The usual safety procedures when working with electrical equipment must be followed and all electrical connections to the filter, inverter & motor must be made by a qualified electrical technician.
      • Filters should be fitted as closely as possible to the incoming mains supply of the wiring enclosure, usually directly after the enclosures circuit breaker or supply switch.
      • Care should be taken to remove any paint etc. from filter and inverter mounting holes and face area of the panel to ensure the best possible earthing of the units.
      • All lead lengths should be kept as short as possible and incoming mains, outgoing motor cables and control cables should be kept well separated. Cable earth screens should only be stripped back as far as necessary to make
        connections - screens should be securely earth bonded to the wiring panel.
 